For the EG4 12k R32 hybrid mini-split, EG4 publishes 12A maximum solar current. For the EG4 24k R32, EG4 publishes 20A maximum solar current. The two 450W examples below have rated short-circuit currents (Isc) numerically between those figures. For either model, review the DC solar input figures below and check the series string’s cold-weather open-circuit voltage (Voc) against the published 380 VDC upper end.
Published DC Input Limits for 12K and 24K Hybrid Units
Both EG4 R32 models accept direct photovoltaic (PV) DC input alongside grid AC power without an external inverter. EG4’s key specifications list 380 VDC as the upper end of the DC solar input range for both R32 models. The key specifications list different lower ends, maximum solar currents, and rated PV inputs for the two models.
| Model | Capacity | AC Input | DC Solar Input Range in Key Specifications | Max Solar Current | Rated PV Input |
|---|---|---|---|---|---|
| EG4 12k Hybrid R32 | 12,000 BTU/h | 115 VAC, 60 Hz | 90 to 380 VDC | 12A | Up to 1,100W |
| EG4 24k Hybrid R32 | 24,000 BTU/h | 208 to 240 VAC, 60 Hz | 150 to 380 VDC | 20A | Up to 2,200W |
EG4’s 24K feature copy lists a DC solar input range of 90 to 380 VDC, while the model-specific key specifications list 150 to 380 VDC.
The 450W panels below have Isc ratings of 14.47A and 16.05A. Both values are above 12A, the EG4 12k R32’s published maximum solar current.
Panel Ratings Used in String Calculations
The string calculations and panel comparisons use four published electrical ratings.
- Open-circuit voltage (
Voc): Voltage with no load. Use the panel’s rating at Standard Test Conditions (STC, 25°C) in the cold-weather calculation. Check cold-adjusted seriesVocagainst the two EG4 R32 models’ published 380 VDC upper end. - Voltage at maximum power (
Vmp). The series table below gives the ratedVmptotals. - Short-circuit current (
Isc). The panel examples compare ratedIscnumerically with EG4’s published maximum solar current figures. - Temperature coefficient of
Voc(Tk_Voc): A negative coefficient, usually given as a percentage per degree Celsius (such as-0.25%/°C). It determines how muchVocrises below 25°C.
Series and Parallel Wiring
According to Renogy’s PV array sizing guide, series wiring adds module voltages. With identical modules in parallel, add their amperages and use one module’s voltage.
Using the panel ratings below, two Philadelphia Solar modules in parallel total 28.94A by rated Isc arithmetic. Two SolarEver modules in parallel total 32.10A by the same calculation. Both totals are above the EG4 24k R32’s published 20A maximum solar current. Two identical parallel modules have a combined rated Isc of 20A or less if each module’s rating is 10A or less. For a 12A comparison, two identical parallel modules rated at 6A each total 12A.
Published Solar Panels Compared Against 12K and 24K Limits
The table compares the ratings of two 450W solar panels from SanTan Solar’s listings.
| Panel Model | Rated Power | Voc | Vmp | Isc | Imp | Panel Isc vs. EG4 Solar Current Ratings |
|---|---|---|---|---|---|---|
| Philadelphia Solar Mono 450W Bifacial | 450W | 38.84V | 33.51V | 14.47A | 13.44A | Above 12A and below 20A |
| SolarEver 450W 96 Half-Cell Mono | 450W | 35.03V | 30.08V | 16.05A | 14.97A | Above 12A and below 20A |
Check cold-weather Voc against the 380 VDC upper end using the calculation below.
Series String Sizing Reference (Rated-Value Arithmetic)
The string totals below are calculated from the published ratings above. Each string exceeds the EG4 24k R32’s published 2,200W solar input rating in rated panel wattage. Always verify winter Voc using your module’s datasheet Tk_Voc before buying.
| Target Unit | Example Panel | Layout | Total Rated Watts | Total Rated Vmp | Total Rated Voc |
|---|---|---|---|---|---|
| EG4 24k R32 | Philadelphia Solar Mono 450W | 5S | 2,250W | 167.55V | 194.20V |
| EG4 24k R32 | Philadelphia Solar Mono 450W | 6S | 2,700W | 201.06V | 233.04V |
| EG4 24k R32 | Philadelphia Solar Mono 450W | 7S | 3,150W | 234.57V | 271.88V |
| EG4 24k R32 | SolarEver 450W 96 Half-Cell | 5S | 2,250W | 150.40V | 175.15V |
| EG4 24k R32 | SolarEver 450W 96 Half-Cell | 6S | 2,700W | 180.48V | 210.18V |
| EG4 24k R32 | SolarEver 450W 96 Half-Cell | 7S | 3,150W | 210.56V | 245.21V |
Five SolarEver 450W panels total 175.15V Voc and 150.40V Vmp by STC arithmetic. That Vmp is 0.40V above the lower end of the 24K DC solar input range in EG4’s key specifications. Six SolarEver panels total 180.48V Vmp and 210.18V Voc by STC arithmetic. Five Philadelphia Solar 450W panels total 167.55V by rated Vmp arithmetic.
Panel Current Comparisons by Model
EG4’s product pages label the 12A and 20A figures as maximum solar current. The comparisons below show where the two panels’ rated Isc values fall relative to those figures.
- Philadelphia Solar Mono 450W Bifacial (
38.84V Voc,33.51V Vmp,14.47A Isc) has a panelIscbelow the EG4 24k R32’s 20A maximum solar current and above the EG4 12k R32’s 12A rating. Five panels total167.55Vby ratedVmparithmetic and2,250Win rated panel power. - SolarEver 450W 96 Half-Cell Mono (
35.03V Voc,30.08V Vmp,16.05A Isc,-0.25%/°C Tk_Voc) has a panelIscbelow the EG4 24k R32’s 20A maximum solar current and above the EG4 12k R32’s 12A rating.
How to Calculate Cold-Weather Maximum String Size
The Victron Energy SmartSolar MPPT Installation Manual warns that panel open-circuit voltage is higher at ambient temperatures below 25°C. Size your string for the lowest expected ambient temperature at your site.
Apply the formula from Renogy’s PV array sizing guide using the EG4 models’ 380 VDC upper end.
Module Voc_max = Voc * [1 + (Tmin - 25) * (Tk_Voc / 100)]
Maximum String Size by Voltage = 380 / Module Voc_max (always round down to a whole panel)
In this equation, Voc is the panel’s rated open-circuit voltage at STC (25°C). Tmin is the lowest expected ambient temperature in °C, and Tk_Voc is the negative percentage temperature coefficient of Voc from the module datasheet.
Worked Cold-Weather Example for the SolarEver 450W Panel
Consider a site where winter temperatures drop to -15°C (5°F, the minimum outdoor heating temperature listed for both EG4 R32 models). Using the SolarEver 450W 96 Half-Cell Mono (Voc = 35.03V, Tk_Voc = -0.25%/°C):
- Subtract STC temperature from
Tmin:-15 - 25 = -40°C. - Multiply by
Tk_Voc / 100:(-40) * (-0.0025) = +0.10(a 10.0% voltage increase). - Calculate cold-adjusted
Vocper module:35.03V * 1.10 = 38.53V(38.533Vunrounded). - Divide 380V by
38.533V:380 / 38.533 = 9.86, which rounds down to 9 panels by voltage alone.
At 25°C STC, the rated Voc of ten SolarEver 450W panels totals 350.30V. At -15°C, the calculated Voc for that 10-panel string is 385.33V, above the 380 VDC upper end. The table below extends the same calculation across three low temperatures.
Design Low Temperature (Tmin) | SolarEver 450W Cold Voc | Max Series Panels by Voltage (<= 380V) | Cold String Voc at Max Count | 6S Cold String Voc | 7S Cold String Voc |
|---|---|---|---|---|---|
0°C (32°F) | 37.22V | 10 panels | 372.19V | 223.32V | 260.54V |
-15°C (5°F) | 38.53V | 9 panels | 346.80V | 231.20V | 269.73V |
-25°C (-13°F) | 39.41V | 9 panels | 354.68V | 236.45V | 275.86V |
Pre-Purchase String Sizing Checklist
Complete these six checks before ordering panels for the EG4 12k or 24k R32.
- Review the DC solar input figures for your model in the table and the note below it. Note the published maximum solar current (12A or 20A).
- Record the panel’s rated
Isc, or add the ratedIscvalues for identical modules in parallel. Use the unit’s published maximum solar current as a numerical reference. - Find your panel’s
Tk_Vocon the manufacturer datasheet. - Calculate
Module Voc_maxat your site’s lowest expected ambient temperature (Tmin), then divide380byModule Voc_maxand round down. - Multiply one panel’s rated
Vmpby the series panel count. Use the result for a numerical comparison with the published DC solar input figures. - Compare total rated panel wattage with your unit’s published PV input rating (up to 1,100W on the EG4 12k R32 or 2,200W on the EG4 24k R32).
Browse the Solar Mini Split Guide archive.
Evidence and Limits
Specifications, maximum solar current figures, and sizing formulas on this page were checked on November 27, 2026, against the official manufacturer product pages, installation manual, and vendor listings cited in the source list. Array wattage and series voltage totals are calculated from published panel ratings. No hands-on testing was performed. Verify the ratings on the datasheet for your equipment before installation.